ABB BC7-30-10-01 BC7 3 Pole Contactor 20 A 5.5 kW 24 V Coil

134,98 ر.ق

  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85365080

Popular Downloads

  • Data Sheet, Technical Information: 1SBC100214C0201
  • Instructions and Manuals: 2CDC102047M6801
  • Dimension Diagram: GJL1200436F0001

Dimensions

  • Product Net Width: 52.5 mm
  • Product Net Height: 57.5 mm
  • Product Net Depth / Length: 46.5 mm
  • Product Net Weight: 0.175 kg

Technical

  • Number of Poles: 3
  • Mini Contactor Type: Mini Contactor
  • Rated Operational Voltage:

    Auxiliary Circuit 690 V AC
    Auxiliary Circuit 250 V DC
    Main Circuit 690 V AC
    Main Circuit 220 V DC

  • Rated Frequency (f):

    Control Circuit DC
    Main Circuit 60 Hz
    Main Circuit 50 Hz
    Main Circuit DC

  • Rated Impulse Withstand Voltage (Uimp):
  • Auxiliary Circuit 6 kV
    Main Circuit 6 kV
  • Rated Insulation Voltage (Ui):

    690 V
    acc. to UL/CSA 600 V

  • Number of Main Contacts NC: 0
  • Number of Main Contacts NO: 3
  • Rated Operational Current AC-1 (Ie):

    (220 / 240 V) 40 °C 20 A
    (220 / 240 V) 55 °C 16 A
    (380 / 440 V) 40 °C 20 A
    (380 / 440 V) 55 °C 16 A
    (690 V) 40 °C 6 A
    (690 V) 55 °C 6 A

  • Rated Operational Power AC-3 (Pe):

    (230 V) Three Phase 3 kW
    (400 V) Three Phase 5.5 kW
    (500 V) Three Phase 5.5 kW
    (690 V) Three Phase, NO 3 kW

  • Rated Short-time Withstand Current (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
  • Number of Auxiliary Contacts NC: 0
  • Number of Auxiliary Contacts NO: 1
  • Rated Operational Current AC-15 (Ie):

    (24 V) 4 A
    (120 V) 4 A
    (500 V) 2 A
    (220 / 240 V) 4 A
    (380 / 400 V) 3 A

  • Rated Operational Current DC-13 (Ie):

    (24 V) 2.5 A
    (110 V) 0.7 A
    (220 / 240 V) 0.4 A

  • Conventional Free-air Thermal Current (Ith): Main Circuit 20 A
  • Rated Control Circuit Voltage (Uc): 24 V DC
  • Coil Operating Limits: (acc. to IEC 60947-4-1) for DC supply 0.85 … 1.1 x Uc (at θ ≤ 55 °C)
  • Degree of Protection:

    Auxiliary Circuit Terminals IP20
    Control Circuit Terminals IP20
    Main Circuit Terminals IP20

  • Mechanical Durability: 10000000 cycle
  • Minimum Switching Capacity:

    Auxiliary Circuit 17 V
    Auxiliary Circuit 5 mA

  • Maximum Electrical Switching Frequency:

    (AC-1) 300 cycles per hour
    (AC-15) 600 cycles per hour
    (AC-3) 600 cycles per hour
    (DC-1) 600 cycles per hour
    (DC-13) 600 cycles per hour
    (DC-3) 600 cycles per hour

  • Connecting Capacity Main Circuit:

    Flexible with Ferrule 1/2x 1 … 2.5 mm²
    Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm²
    Flexible 1/2x 1 … 2.5 mm²
    Rigid 1/2x 1 ..

Contact for price
SKU: 9049821449 Category:

Additional information

UPC

040048820574

Reviews

There are no reviews yet.

Be the first to review “ABB BC7-30-10-01 BC7 3 Pole Contactor 20 A 5.5 kW 24 V Coil”